§ 77.802. Protection of high-voltage circuits; neutral grounding resistors; disconnecting devices.
124 words·~1 min read·
/us/cfr/t30/s§ 77.802·A research copy — for the controlling text, always check the official state or federal source. Not legal advice.
High-voltage circuits supplying portable or mobile equipment shall contain either a direct or derived neutral which shall be grounded through a suitable resistor at the source transformers, and a grounding circuit, originating at the grounded side of the grounding resistor, shall extend along with the power conductors and serve as a grounding conductor for the frames of all high-voltage equipment supplied power from that circuit, except that the Secretary or his authorized representative may permit other high-voltage circuits to feed stationary electrical equipment, if he finds that such exception will not pose a hazard to the miners.
Disconnecting devices shall be installed and so equipped or designed in such a manner that it can be determined by visual observation that the power is disconnected.